This 110mm pipe collar will seal flammable pipes 110mm diameter and can be face fixed in a wall or ceiling structure. They are suitable for use on concrete, masonry and plasterboard partitions for up to 240 minutes.
Pyroplex® Intumescent Pipe Collars have been specifically designed to prevent the passage of fire and hot gases through:
Product features
Installation instructions
Ensure substrate around 110mm pipe is flat and free from obstructions – if necessary make good by using Pyroplex® Intumescent Acrylic Sealant.
Release retaining pin and position intumescent pipe collar around pipe.
Slide tab through slot in intumescent pipe collar and fold back 180 Degrees to secure.
Secure intumescent 110mm pipe collar by drilling holes in structure by using fixing lugs as template. To fix use M8 x 65mm sleeve anchors or 50mm [minimum] expanding bolts.
When the intumescent collar has been securely fitted into place any residual gaps between the intumescent collar and the substrate can be filled using Pyroplex® Intumescent Acrylic Sealant.
Product testing
Pyroplex Limited have carried out independent fire resistance tests to confirm the suitability of the product and to demonstrate product compliance by utilising BS 476: Part 20: 1987 and BS EN 1366-3: 2004. EN Classification report to BS EN 13501-2: 2007 is available on request.
Brand: Pyroplex
Use Case: Fire
Applications: Walls, Floors
Test Certification: BS 476: Part 20: 1987 and BS EN 1366-3: 2009 and has a European classification in accordance with BS EN 13501-2: 2007
Fire Rating: 120 Minutes
Finish: Galvanised Steel
Fixing: M8 x 65mm sleeve anchors or 50mm [minimum] expanding bolts
Included: 1 x Pyroplex Intumescent Pipe Collar 110mm 2 Hour Rated
Diameter: 110mm
To Suit Pipe: 110mm
Height: 60mm
Shell O/D: 135mm